The METRISO G1000* insulation and resistance measuring instruments allow
for quick and effective testing of protective measures in accordance with:

- DIN VDE 0100
- ÖVE-EN 1 (Austria)
- SEV 1000 (Switzerland)
- and regulations specific to other countries as well
Insulation measurement per EN 61557-2 / VDE 0413 part 2
Low-resistance measurement per EN 61557-4 / VDE 0413 part 4
Voltage testing and measurement up to 1000 V
- Digital and analogue display, backlit
- Signalling of dangerous contact voltage
- Overvoltage protection - protects the instrument in the event of
inadvertent connection to mains power
- Fuse link for all resistance measuring ranges
- Voltage measurement up to 1000 V
- Compact and rugged - for service calls under harsh conditions and laboratory use
- One measuring point self-test
with test resistance of 10 MΩ per EN 50110 / VDE 0105-100
- Polarization index and absorption ratio
The insulation measuring instruments are suitable for the following tasks:
- Measurement of insulation resistance at voltage-free devices and systems,
up to 1000 V
- Testing of the resistance of earthing conductors, protective conductors
and equipotential bonding
- Checking of test objects for absence of voltage
- Testing of electrostatic discharge capacity at floor coverings (using
shielded measurement cables) - EN 1081
| |

new |
|
new
|
|
|
| METRISO |
G1000+ |
G1000 |
G1000A |
G500 |
G500MM |
| Article number |
M550B |
M550C |
M542A |
M550D |
M550E |
| Measurements |
|
|
analog |
|
|
| PI, DAR Polarization index measurements |
x |
- |
- |
- |
- |
Riso Uvariable =
50 ... 1000 V
(Limit value 1 MΩ) |
x |
- |
- |
- |
- |
Riso URamp =
50 ... 1000 V
Display of breakdown voltage |
x |
- |
- |
- |
- |
| Measuring ranges Riso |
10 k ...
...1 TΩ |
10 k ...
200 GΩ |
100 k ...
100 GΩ |
10 k ...
100 GΩ |
10 k ...
100 GΩ |
| Riso U = 50, 100, 250, 500 /
1000 V |
x / x |
x / x |
x / x |
x / - |
x / - |
| R 10 Ω... 10 kΩ |
x |
x |
- |
x |
x |
| RLO 0,01 ... 10
Ω |
x |
x |
x |
x |
- |
| U 0 ... 500 /
1000 V |
x / x |
x / x |
x / x |
x / - |
x / - |
| Display functions |
|
|
|
|
|
| Backlit display |
x |
x |
x |
x |
x |
Limit value LED Limit (green/red)
Additional acoustic signal, limit value per VDE 0100 |
Riso, RLO |
Riso, RLO |
Riso, RLO |
Riso, RLO |
Riso,
- |
| LED for dangerous contact voltage (when switched off) |
x |
x |
x |
x |
x |
| LCD symbol for external voltage |
x |
x |
x |
x |
x |
| Battery level display |
x |
x |
x |
x |
x |
| Special functions |
|
|
|
|
|
| Data storage in the instrument, 50.000 objects |
x |
- |
- |
- |
- |
| Discharge capacitive devices under test |
x |
x |
x |
x |
x |
| Safety shutdown (UBatt < 8 V) |
x |
x |
x |
x |
x |
| Features |
|
|
|
|
|
| Charging socket, RS232 and USB interface |
x |
- |
- |
- |
- |
| Measuring categories CAT II 1000V, CAT III 600V |
x |
x |
x |
- |
- |
| Measuring category CAT III 600V, CAT IV 300V |
x |
x |
x |
x |
x |
| Integrated 10 MΩ test resistor |
x |
x |
x |
x |
- |
DAkkS calibriation certificate in scope of delivery
(W = Proprietary certificate " ) |
x |
x |
(W) |
x |
x |
Practical sets wit remote triggering and ever-ready case
|