U1387

Active Energy, 3-Wire 3-Phase Current, PTB Approval, 1//5 A, LCD

The U1387 energy meter acquires active energy in 3-wire, three-phase current systems via current transformers, and can be used universally for measuring and billing electrical energy in household, industrial and building management applications. Type approval and calibration allow for official billing of electrical energy to third parties. Momentary circuit loads can be evaluated at any time with the help of the additional instantaneous power display.

S0 Pulse Output / <hsdlimg  SRC= / / L-Bus

Integrated error recognition for incorrect phase sequence, missing phases, current transformers with reversed polarity, measuring range overloads and missing bus connections saves valuable time and test equipment during troubleshooting.

  • new: Connection with Kieback&Peter DDC3000 via SBM5x/04
  • Active energy measurement (import) per EN 61036, class 1
    with electronic anti-reversing
  • Instantaneous power for the evaluation of momentary circuit loads
  • Can be expanded for additional measured mains quantities
  • 5//1 transformer connection, adjustable, calibratable transformation ratios
  • Export variant available for 60 Hz line frequency
  • Displays installation errors without additional measuring equipment
  • S0 pulse output or 230 V, adjustable pulse rate and pulse duration
  • Label field for individualized identification
  • Meter readings can be optionally viewed when the electrical circuit is switched off
  • Minimal space requirements thanks to compact design
  • Mounts to DIN rail per EN 50022
  • Type approval: PTB, BEV, metas, DZNM

More Transparence During Actual Operation
In addition to active energy and instantaneous power, the multifunctional variant (M1) also displays individual phase current, voltage, active, reactive and apparent power, power factor and frequency by simply pressing a key. Voltage level, individual phase utilization, reactive power component and compensation can thus be continuously evaluated during operation.

Universal Bus Interface
The energy meters transmit meter readings and other data to data logging, billing and optimizing systems, as well as building automation and control technology applications, via optional interfaces.

  • LON interface with FTT-10A transceiver (W1)
  • M-bus interface per EN 1434-3 (W2)
  • L-bus interface for battery operated HYDRO-RADIO 868 radio module (W3)

Diverse Calibration Capability - Approved for Official Billing
The energy meters can be supplied as calibrated variants (P1), and additionally with calibration certificate (P2), for official energy billing. In accordance with legal requirements, the calibration certificate may not show any measurement error. Depending upon requirements, the following variants are possible:

  • Calibrated main display for primary energy, transformation ratios specified with the order can be fixed (Q9) and calibrated, calibrated pulse output with reference to primary energy and a fixed pulse rate based upon CTxVT (V1,V3)
  • Calibrated main display for secondary energy, fixed transformation ratios CT=VT=1 (Q0), calibrated pulse output with reference to secondary energy and a fixed pulse rate of 1000 pulses per kWh (V1, V3)
  • Uncalibrated main display for primary energy, adjustable transformation ratios (Q1) in combination with calibrated auxiliary display for secondary energy, calibrated pulse output with reference to secondary energy and a fixed pulse rate of 1000 pulses per kWh (V1, V3)

Meter Reading and Bus Operation with Electrical Circuit Switched Off
The meter can be optionally equipped with a 24 V DC auxiliary power input (H1) for assured discharge-free voltage, which allows for direct meter reading, or remote meter reading for bus compatible variants, even when the electrical circuit is switched off. Meter reading is possible without continuously active supply power with the help of the UBAT-24V battery pack.

Type 

U1381 U1387 U1389
Alternating current 2-wire x    
3-phase current 3-wire   x  
4-wire     x
Voltage (V) Direct 230 400/500 400
Transformer - 100..110 100..110
VT   (prog.) (prog.)
Current (A) Direct - - -
Transformer 5//1 5//1 5//1
CT (prog.) (prog.) (prog.)
Pulse output Import S0
(230 V)
S0
(230 V)
S0
(230 V)
Rate (prog.) (prog.) (prog.)
Duration (prog.) (prog.) (prog.)
Interface LON (x) (x) (x)
M-bus (x) (x) (x)
L-bus (x) (x) (x)
Display
Installation error
  x x x
Can be calibrated   x x x
Accuracy Class 1 1 1
Active power display   x x x
Multifunction Variant
with additional
measurement of 
U, I, P, Q
S, PF, f
(x) (x) (x)
Type approval DE-PTB x x x
AT-BEV   x x
CH-metas x x x
HR-DZNM x x x

(x) = optional

 

  Article No: U1387
Icon Technical Data » GB » F » I » E (pdf 159 kB)
Icon Operating Instructions » GB » F » I » E (pdf 305 kB)
Icon Pamphlet LCD Meter Series » GB » NL » CZ (pdf 176 kB)
Installation Instruction D-GB-F-I (pdf 186 kB)
LON Installation (XIF, Plug-In) (zip 155 kB)
Icon LON Interface Documentation » GB » F (pdf 642 kB)
M-Bus Configuration Software MBCONF (zip 917 kB)
M-Bus Interface Documentation (pdf 158 kB)
M-Bus and Remote Meter Reading (pdf 641 kB)
M-Bus Connection to Kieback&Peter DDC3000 (pdf 43 kB)
L-Bus Interface Documentation (pdf 157 kB)
PTB Approval (pdf 338 kB)
PTB Approval - Completion1 (pdf 505 kB)
PTB Approval - Completion2 (pdf 357 kB)
PTB Approval - Completion3 (pdf 357 kB)
PTB Approval - Completion4 (pdf 152 kB)
PTB Approval - Completion Feature 9 (pdf 356 kB)
BEV Approval (pdf 188 kB)
BEV Approval - Completion1 (pdf 98 kB)
metas Approval - with Completions (pdf 1231 kB)
DZNM Approval (pdf 305 kB)
CMI Approval (pdf 112 kB)
Inquiry forms for RFQ (xls 40 kB)
Software MBCONF
Accessories (display)