DHTML Menu, (c)2004 Apycom PROFITEST MASTER
World-Map
  Home » Products » Electrical Testing » Testing of Electr. Installations
 

PROFITEST MASTER

Range of Test Instruments for VDE 0100 / IEC 60364.6 (new)

A broad-range measuring device allows for use of the test instrument in all alternating and 3-phase electrical systems with voltages from 65 to 500 V and frequencies of 15.4 to 420 Hz.

   Standard   at 300 V   at 600 V

 
  • Loop and line impedance measurement
  • Measurement of insulation resistance using nominal voltage, with variable or rising test voltage
  • Low-resistance measurement
  • Earth resistance measurement
  • Standing-surface insulation measurement
  • Universal connector system
     

Special features:

  • Display of approved fuse types for electrical systems
  • Energy meter start-up testing
  • Calculation of cable lengths for common copper wire cross-sections
  • Measurement of biasing, leakage and circulating current of up to 1 A, as well as working current of up to 150 A with Clip 0100S current sensor clamp as accessory
  • Phase sequence measurement (including highest line-to-line voltage)
     

 Testing of residual current devices (RCCBs)

  • Measurement of contact voltage without tripping the RCCB.
    Contact voltage is measured with reference to nominal residual current using 1/3 of the nominal residual current value.
  • Tripping test with nominal residual current, tripping time measurement
     

Special tests for systems and RCCBs

  • Testing of equipment and RCCBs with rising residual current including indication of tripping current and contact voltage at the moment the RCCB is tripped
  • Testing of RCCBs with: ½ × IN, 1× IN, 2× IN, 5× IN
  • Testing of RCCBs which are suitable for pulsating residual direct current; testing is conducted with positive or negative half-waves
  • Testing of RCCBs with adjustable residual current for determining contact voltage
     

Testing of special RCCBs (with PROFITEST MTECH)

  • Selective S, SRCDs, PRCDs (Schukomat, Sidos and others), types G/R, AC, A and B
     

Testing of RCCBs in IT systems
 

PROFITEST MBASE  MTECH 
     
RCD measurements    
UB measurement without tripping the RCCB x x
Tripping time measurement x x
Tripping current measurement x x
Selective, SRCDs, PRCDs, type G/R x x
AC/DC sensitive RCDs, type B - x
Loop impedance, ZL-PE / ZL-N    
Fuse table for systems without RCD x x
Without tripping the RCD, fuse table - x
With 15 mA test current without tripping the RCD x x
Earth resistance RE    
I/U measuring method, mains powered x x
Selective earth resistance
with probe, earth electrode and current clamp
x x
Earth loop resistance REloop
with 2 clamp meters
- -
Equipotential bonding measurement RLO    
Automatic polarity reversal x x
Insulation resistance RISO    
Variable or rising test voltage x x
Voltage measurement    
UL-N / UL-PE / UN-PE / f x x
     
Special measurements    
Leakage current (clamp meter measurement) x x
Meter start-up x x
Phase sequence x x
Standing-surface insulation ZST x x
Earth leakage resistance RE (ISO) x x
     
Features    
Selectable user interface language x x
Memory (database for up to 50,000 objects) x x
RS 232 port for scanner x x
USB port for data transmission x x
ETC user software for PC x x
Measuring category CAT III 600 V / CAT IV 300 V x x
DKD calibration x x
Article number  M520M M520o

 

  Article No: M520M M520o
myGMC Icon myGMC: News and informations about PROFITEST MASTER
Icon Technical Data » GB » F » I (pdf 535 kB)
Icon Operating Instructions » GB » F » I » E » NL » P » FI (pdf 1343 kB)
Short-form Operating Instructions (pdf 675 kB)
Icon Pamphlet » GB » F  » I  » NL (pdf 3203 kB)
Software ETC
Software PC.doc-ACCESS
Software PC.doc-WORD/EXCEL
Software USB2COM PS
Accessories (display)